Distances from ground reservoirs with capacity more than 2000 m

3

 are received 

according to B.2.2-58.1 [14]. 

Distances from the devices for pouring out and pouring in of railway or motor-car 

tanks to the buildings and constructions of an enterprise mustn’t be less than 15 m, 
except buildings and constructions of G category, the distance to them mustn’t be less 
than 40 m. 

Pouring out of winematerials is allowed on one area of the railway gauge only 

with separate pouring out and pouring in devices and pipelines. 

Introduction of railway gauges into the premises of A and B categories is not 

allowed. 

It is banned to surround the areas, overpasses and platforms for loading and 

unloading of fuel, tableware, packages and so on, within dead-end siding railway 
gauges for receiving alcohols. 

Requirements to volumetric and planning and constructive decisions 
Production and storage buildings of A and B categories must meet the 

requirements of the 1

st

; 2

nd

 and 3

rd

 degrees of fire resistance [15]. Buildings of the 1

st

 

and the 2

nd

 degrees of fire resistance are allowed to design with 3 storeys, and of the 

3

rd

 A degree – with 1 storey. 

Premises of A and B categories should be located near outer walls, and in 

multistory buildings – on the upper floor. It’s banned to design suspended ceilings in 
them. Premises of A and B categories are not located directly over or under the 
premises, designed for simultaneous staying of more than 50 people. It’s not allowed 
to locate production and storage premises of A and B categories on the ground floort 
and basement as well as in the buildings with attics.  

In front of the lifts in the premises of A and B categories it is foreseen to make 

platform-sluices of the 1

st

 type with constant prop of the air not less than 20. The doors 

of platform-sluices from the side of the lift shafts are made of materials without glazing 
non-flammable. Engine-rooms of the lifts are also provided with constant prop of the 
air. 

The floors in the premises of A and B categories are made of non-flammable 

materials with covering which doesn’t create sparks. Inclines of the floors to ladders 
are made with 0,1-0,2 % incline. Under-floor canals (for laying of the communications) 
are filled up with sand or any other non-flammable material for making impossible 
accumulation of vapours of HIL or liquids in them. 

Storage building with shelving preserving of barrels with height of preservation 

more than 5,5 m must have torches or ventilating shafts on the roof for smoke 
removing. In the zone of arrangement of cross passages between shelving’s, doorways 
in the outer walls should be foreseen. 

Fitted premises for automation panels must meet the following requirements  