– floors must be non-electro-conductive; 
– to be separated from premises of A and B categories with dust and gas-proof, 

fire-fighting partitions of the 1

st

 type;  

– to have independent exits outside, into the corridor or into the outlet grid;  
– connection with production premises of A and B categories (if necessary) is 

allowed to make through platform-sluices with the doors which have devices for self-
closing; 

– premises mustn’t be located over and under premises of A and B categories, 

under shower-baths, lavatories cum bathrooms, under production premises with wet 
technological processes, under ventilator inflowing chambers; 

– for excluding the possibility of leaking the liquids into premises, the liquids, 

which take part in the technological process, the floor in the premises for automation 
panels is raised by 0,15 m with respect to the floor of the adjacent premises of A and 
B categories during arranging of the bottom of canals or double floor; 

– distance across and down from the outer doors and windows of the premises for 

automation panels to the outer doors and windows of the premises with highly 
explosive zones N1 and N2, is not less than 4 metres to the windows which can’t be 
opened and 6 metres to the windows which can be opened. 

The distance to the windows with glass blocks of 0,1 m width isn’t standardized. 
The department of distillation of home-brewed beer and rectification department 

for obtaining alcohol, utilization of wastes are locate in separate premises. To locate 
production and subsidiary premises over and under them is banned. 

The raw material and packaging materials in production premises are located in 

an open way or behind the net, measuring according to the demand.  

The equipment with inflammable liquids (HIL) is banned to locate: 
– over and under the administrative and consumer premises; 
– under overpasses of the technological pipelines with inflammable, highly 

explosive and caustic substances; 

– over the areas of open pumping and compressor plants, except cases of 

application hermetic ones without pumps of hydroseal type or during fulfilling of 
special measures of safety. 

The areas of overlapping and technological platforms, micromodule stacks, where 

the equipment with HIL is mounted, must have solid floor or a pan with blind edges of 
0,15 m high, made of non-combustible materials, and in the places of an exit to the 
stairs, fixed ramps, of not less than 0,8 m wide, are made Slope of fixed ramps must be 
not less that 16 % when locating in the closed premises and not more, than 10 % when 
locating outside. The platforms are provided with ladders for pipe-bending of liquids 
into hermetic reservoirs. 