Mounting of thresholds in the door openings on the ways of evacuation higher 

that 0,05 m, isn’t allowed. 

Open storehouses of ethyl alcohol are located in the open platforms in reservoirs 

and packages. It’s allowed to locate them under the shed with a net fence. The 
reservoirs are mounted on concrete (metal) supports, raised over the level to concrete 
watertight covering (incline to a rain-receiver – 1,0 %) – not more than 1,0 m for 
examination of a reservoir bottom. For protection against sunlight they are painted with 
light colours. Ground reservoirs are protected by the wall or solid ground shaft. The 
volume, created by the wall or ground shaft, must be equal to the full capacity of the 
biggest reservoir. The height of the outer fence must be by 0,2 m higher that the 
calculated level of the liquid that spilled, but not more than 1,0 m and the width of the 
solid shaft from above – 0,5 m. The distance from the walls of reservoirs to the 
basement of the inner slopes of the ground shaft or protecting walls is not less than 
3,0 m.  

Distance between ground reservoirs, that are located in one group is not less than 

0,5 diameter of the ground reservoir. 

When choosing reservoirs for storage of HIL, additional reservoirs, designed for 

emergency overflow, which aren’t included in the calculation of the general capacity 
of the storehouse, are provided. They are constantly empty, Washed and cleaned from 
HIL Vapours. In this situation, setting up of special emergency capacities outside the 
building isn’t foreseen. Emptying of reservoirs for storage of HIL must be carried out 
by food pumps into reserve reservoirs of the storehouse or special emergency ones. 
The capacity of the emergency reservoir must be not less than the capacity of the 
biggest reservoir of the storehouse.  

An emergency discharge of HIL is carried out from one of the closed hermetic 

apparatuses under excessive pressure of water vapour or inert gas. The pipelines for 
emergency discharge should be of minimum extension, with minimum amount of 
turnings and branches and incline not less than 0,2 % to the side of emptying. The 
pipelines mustn’t have key accessories, except disconnecting accessories of the 
apparatuses and reservoirs. 

It a gravity flow of EJL is carried out into an emergency reservoir, then the 

diameter of the pipeline must be not less than 100 mm with the devices which warn 
against the possibility of fire spreading. The pipeline must have a key device. The 
emergency reservoir is located outside the building at the distance of not less than 1 m 
from the walls without openings and not less than 5 m from the walls with openings. 

The equipment, apparatuses, communications and accessories in the premises of 

A and B categories must be hermetic, from the materials, which don’t create sparks. 
For technological apparatuses which require constant observation, the premises 
(cabins, compartments) are equipped with hermetic inspection windows of minimum 

- 1752 -