building with the biggest volume and increased fire and explosion danger. Expenses 
for cooling the ground reservoirs during 3 hours and diluting of alcohol in a reservoir, 
which is on fire, to 70 % concentration are included into the calculation of water 
expenses for fire extinguishing. 

For the premises of A and B categories, reserved fire-prevention funds of water 

in fire reservoirs are renewed after the fire, not later than 24 hours. Fire reservoirs and 
their equipment are protected against water freezing. 

In case of impossibility of water intake from the fire reservoir, accepting (wet) 

wells with volume not less than 3 m

3

, connected with fire water storage pipeline, the 

diameter of which is not less than 0,2 m, are foreseen. In front of the accepting well, 
on the connecting pipeline, it is necessary to locate the shutter with, leading under the 
cover, steering wheel in a separate well. 

Fire hydrants, “wet” wells of fire reservoirs, pumping stations of fire-prevention 

water supply are located not closer than 40 m from ground reservoirs for alcohol and 
not closer than 10 m from the buildings of A and B categories. 

Fire-prevention water supply is carried out through fire hydrants, located on the 

ring system of the connected fire-prevention and economic water-supply at the distance 
not more than 130 m from each other. 

All reservoirs for storage of ethyl alcohol must be equipped: 
– with stationary system of irrigation for cooling the roof and the walls of the 

reservoirs during the fire; 

– with the system of water delivery into reservoirs for diluting the alcohol during 

the fire. 

Cooling of the roof and walls of the reservoirs with alcohol during the fire is 

carried out by slotted sector sprinklers, mounted on the ring from steel pipes with 
diameter not less than 75 mm. The intensity of irrigation is 0,5 l/s per one metre of the 
reservoirs perimeter.  

When locating wine-making enterprises at the distance of 200 m from natural 

reservoirs with guaranteed supply and level of water, the approaches with hard 
surfacing, grounds of 1212 m size and piers for water intake by a fire vehicle at any 
season of the year, are made. In this case fire reservoirs are not built. 

Water supply for cooling and extinguishing of ground reservoirs of general 

capacity up to 400 m

2

 at the enterprises, which are located beyond the limits of 

populated areas, is carried out from fire reservoirs. The amount of reservoirs must be 
not less than 2 with their calculated capacity, but not less than 100 m

3

. The distance 

from fire reservoirs to the enterprise is not more than 150 m. 

For preventing from getting into sewerage and spreading of HIL in it, sewer 

discharges in the technological apparatuses must have flange joints on the pipelines for 
installation plugs during repair of the apparatuses. Discharge of sewage into sewerage 

- 1756 -