Figure 8. Averaged day operating cycle of the experimental adsorptive heat pump  
 
Adsorber was filled with 10 kg of the composite ‘silica gel – sodium sulphate’. 

Mineral wool with thickness of 100 mm and heat conduction coefficient 0.035 W/m·K 
was used as heat insulator. The adsorbent was regenerated at night from 0.00 to 8.00 
a.m. In a day time discharge is performed. So, heat pump supplied heating system with 
water warmed to 45 – 35°C. 

The efficiency criterion for adsorptive heat pumps is coefficient of energy 

performance COP.  СОР is calculated by two methods:  

1)

 

as ratio of adsorption heat to sum of desorption heat and external heat  supplied 

to adsorbent during its heating upto regeneration temperature (СОР

c

); 

2)

 

as ratio of adsorption heat to heat supplied by solar collector (СОР

s

(b)) (net). 

Results of calculation are given in Table 1.  

Table 1 Adsorptive heat pump coefficient of energy performance  

Month 

The total average daily value of solar 

radiation (kW-h/m

2

‘silica gel – Na

2

SO

4

’ 

СОР

СОР

s

(b) 

May 

5.99 

2.084 

1.130 

June 

5.86 

2.084 

1.133 

July 

6.06 

2.084 

1.128 

August 

5.66 

2.084 

1.137 

September 

4.41 

2.084 

1.176 

 